HVAC Duct Sizing Calculator is a paid API for AI agents from x402-agent-api.onrender.com, paid per call via x402, $0.002/call, status unknown (last checked 2026-10-10).
Calculates HVAC duct dimensions (round or rectangular) from airflow, velocity, and/or friction rate using ASHRAE Darcy-Weisbach methods, returning step-by-step engineering calculations.
HVAC duct sizing calculator: any two of duct size (round or rectangular), airflow, velocity and friction rate. Round and rectangular equivalents, nearest standard sizes, friction loss per 100 ft (Darcy-Weisbach, Colebrook), velocity pressure, design checks. Equal-friction sizing, fixed-depth ducts, IP or SI. Shows every step with the numbers. $0.002 USDC per call.
Returns the solved duct dimension (diameter or rectangular width×height), air velocity, friction rate, Reynolds number, aspect ratio check, a list of nearest standard sizes with best-fit flag, numbered step-by-step calculations with ASHRAE chapter references, unit-system-appropriate values, design range checks (velocity and friction), and suggested follow-on HVAC tool calls (e.g. coil load) with arguments.
POSThttps://x402-agent-api.onrender.com/api/v1/hvac-duct-size?utm_source=zero.xyzUse this endpoint when you need HVAC duct sizing calculations with full engineering transparency — step-by-step Darcy-Weisbach derivations, ASHRAE citations, standard size lookup, and design range validation — rather than a black-box result. Ideal for engineering agents, MEP design workflows, or any scenario requiring auditable calculations in either IP or SI units. Prefer over generic calculators when ASHRAE-referenced intermediate steps and standard size tables are needed.
| Field | Type | Description |
|---|---|---|
| units | string | "IP" (°F, CFM, in, BTU) or "SI" (°C, L/s, mm, kW). Default IP. Applies to inputs and results. |
| width | number | Rectangular width: in or mm. With height, the duct size; alone, a fixed side (e.g. a ceiling depth) the other side is solved for. |
| height | number | Rectangular height: in or mm. |
| airflow | number | Airflow: CFM (IP) or L/s (SI). |
| diameter | number | Round duct diameter: in (IP) or mm (SI). |
| velocity | number | Air velocity: FPM (IP) or m/s (SI). |
| friction_rate | number | Friction loss: in. w.g. per 100 ft (IP, typically 0.05-0.15) or Pa/m (SI, typically 0.4-1.2). With airflow, this is equal-friction sizing. |
{
"type": "json",
"example": {
"notes": [
"The rectangular size has the same friction loss and airflow as the round duct (ASHRAE equivalent diameter); its velocity is lower because its area is larger.",
"Galvanized steel (ε = 0.0003 ft) and standard air (0.075 lb/ft³, 70 °F, sea level). Fittings and transitions are not included.",
"For design guidance; the engineer of record is responsible for final selections."
],
"round": {
"area": 1.1112,
"diameter": 14.27,
"velocity": 900,
"friction_rate": 0.08,
"standard_sizes": [
{
"best_fit": true,
"diameter": 14,
"velocity": 935,
"friction_rate": 0.088
},
{
"best_fit": false,
"diameter": 16,
"velocity": 716,
"friction_rate": 0.0457
}
]
},
"steps": [
{
"step": "Round diameter at the friction rate (equal friction)",
"reference": "ASHRAE Handbook—Fundamentals (2021), Ch. 21 Duct Design",
"calculation": "Iterated the diameter (bisection) until the Darcy-Weisbach friction loss at 1,000 CFM equals 0.0800 in. w.g./100 ft → D = 14.27 in"
},
{
"step": "Square equivalent",
"reference": "ASHRAE Handbook—Fundamentals (2021), Ch. 21 Duct Design (Huebscher equivalent diameter)",
"calculation": "For W = H = S: De = 1.30·S^1.25 / (2S)^0.25 = 1.09317·S → S = 14.27 / 1.09317 = 13.06 in"
},
{
"step": "Round duct: Reynolds number",
"reference": null,
"calculation": "Re = D·V / ν = 1.1895 ft × 14.998 ft/s / 1.56×10⁻⁴ ft²/s = 114,361"
}
],
"units": "IP",
"checks": {
"friction": "Typical design range (0.04-0.15 in. w.g./100 ft; about 0.3-1.2 Pa/m).",
"velocity": "Normal design range (400-2,500 FPM; about 2-12.7 m/s).",
"aspect_ratio": null
},
"airflow": 1000,
"velocity": 900,
"next_calls": [
{
"why": "What cooling load does 1000 CFM carry from 80/67 to 55/54 °F?",
"tool": "hvac_coil_load",
"price": "$0.002",
"arguments": {
"units": "IP",
"airflow": 1000,
"leaving": {
"dry_bulb": 55,
"wet_bulb": 54
},
"entering": {
"dry_bulb": 80,
"wet_bulb": 67
}
}
}
],
"references": [
"ASHRAE Handbook—Fundamentals (2021), Ch. 21 Duct Design",
"SMACNA HVAC Duct Design Manual (standard sizes, aspect ratio guidance)"
],
"solved_for": "size",
"inputs_used": {
"airflow": 1000,
"friction_rate": 0.08
},
"rectangular": {
"area": 1.184,
"basis": "equal_friction",
"width": 13.06,
"height": 13.06,
"velocity": 845,
"aspect_ratio": 1,
"friction_rate": 0.08,
"standard_sizes": [
{
"width": 14,
"height": 14,
"best_fit": false,
"velocity": 735,
"aspect_ratio": 1,
"friction_rate": 0.0568,
"equivalent_diameter": 15.3
},
{
"width": 16,
"height": 12,
"best_fit": false,
"velocity": 750,
"aspect_ratio": 1.33,
"friction_rate": 0.0605,
"equivalent_diameter": 15.11
}
],
"equivalent_diameter": 14.27
},
"unit_labels": {
"area": "ft²",
"load": "MBH (1,000 BTU/h)",
"grains": "gr / lb dry air",
"length": "in",
"airflow": "CFM",
"density": "lb / ft³",
"enthalpy": "BTU / lb dry air",
"pressure": "psia",
"velocity": "FPM",
"elevation": "ft",
"condensate": "gal / h",
"temperature": "°F",
"friction_rate": "in. w.g. / 100 ft",
"humidity_ratio": "lb water / lb dry air",
"specific_volume": "ft³ / lb dry air",
"relative_humidity": "%",
"velocity_pressure": "in. w.g."
},
"friction_rate": 0.08,
"primary_shape": "round",
"friction_factor": 0.01885,
"reynolds_number": 114361,
"velocity_pressure": 0.0505
}
}No reviews yet. Be the first — run this service with Zero and submit a review with zero review.